Danfoss ECL Comfort 210 Installation Manual page 77

Application a230
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
Infl. - min. (compensation temp., 1. point)
Circuit
1
Determines how much the desired flow temperature will be influenced if the
compensation temperature is lower than the set limit.
Influence higher than 0:
The desired flow temperature is increased, when the compensation
temperature gets below the set limit.
Influence lower than 0:
The desired flow temperature is decreased, when the compensation
temperature gets below the set limit.
Danfoss District Energy
ECL Comfort 210, application A230
11063
Setting range
Factory setting
-9.9 ... 9.9
0.0
Example
The limit value is set to 5 °C.
'Infl. min. ' is set to 2.5.
The actual compensation temperature is 2°C (3 degrees below the
limit value).
Result:
The desired flow temperature is changed by 2.5 x 3 = 7.5 degrees.
VI.LG.H1.02
DEN-SMT/DK
77

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl comfort 310

Table of Contents