Setting of desired flow temperature when the ECL controller is in comfort
mode.
Des. T Saving
Circuit
1
Setting of desired flow temperature when the ECL controller is in saving
mode.
Temp. max. (flow temp. limit, max.)
Circuit
1
Set the max. flow temperature for the system. The desired flow
temperature will not be higher than this setting. Adjust the factory
setting, if required.
Temp. min. (flow temp. limit, min.)
Circuit
1
Set the min. flow temperature for the system. The desired flow
temperature will not be lower than this setting. Adjust the factory
setting, if required.
Danfoss District Energy
ECL Comfort 210, application A230
11018
Setting range
Factory setting
-30.0 ... 30.0 °C
7.5 °C
11019
Setting range
Factory setting
-30.0 ... 30.0 °C
25.0 °C
11178
Setting range
Factory setting
–30 ... 50 °C
30 °C
11177
Setting range
Factory setting
–30 ... 50 °C
0 °C
This setting has no influence if the controller receives an external value
for the desired flow temperature.
This setting has no influence if the controller receives an external value
for the desired flow temperature.
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .
VI.LG.H1.02