Circuit
1
Determines how much the desired flow temperature will be influenced if the
return temperature is higher than the set limit.
Influence higher than 0:
The desired flow temperature is increased, when the return
temperature gets higher than the set limit.
Influence lower than 0:
The desired flow temperature is decreased, when the return
temperature gets higher than the set limit.
Infl. - min. (return temp. limitation - min. influence)
Circuit
1
Determines how much the desired flow temperature will be influenced if the
return temperature is lower than the set limit.
Influence higher than 0:
The desired flow temperature is increased, when the return
temperature gets below the set limit.
Influence lower than 0:
The desired flow temperature is decreased, when the return
temperature gets below the set limit.
Danfoss District Energy
ECL Comfort 210, application A230
11035
Setting range
Factory setting
-9.9 ... 9.9
0.0
11036
Setting range
Factory setting
-9.9 ... 9.9
2.0
Example
The return limit is active above 20 °C.
The influence is set to 0.5.
The actual return temperature is 2 degrees too high.
Result:
The desired flow temperature is changed by 0.5 x 2 = 1.0 degree.
Example
The return limit is active below 20 °C.
The influence is set to 2.0.
The actual return temperature is 2 degrees too low.
Result:
The desired flow temperature is changed by 2.0 x 2 = -4.0 degrees.