Switching on detector zones / detectors
⇒
When there is no event with a higher priority, isolations (switched off) are directly indicated on the display. You
may then directly proceed with Step 3 below.
⇒
When all zones within a section (a zone is a detector in this system's terminology) are turned off, the section is
additionally indicated as switched off.
⇒
Detectors that still contain smoke or test gas cannot be switched back on.
Step
1.
Press the button
(password required)
Press <1> "Message summary".
2.
Press <4> "Isolations".
3.
Scroll with the navigation buttons to the
isolation (detector e.g. Reception, or zone
e.g.Ground Floor) you want to switch on.
The selected isolation is marked by a frame.
Press Softkey <1> "Execute command".
Press <1> "ON".
4.
Procedure in case of Fault
Step
1.
Press <Silence buzzer> on the PMI.
2.
Read message/fault location on the display.
3.
Press <Acknowledge> on the PMI.
4.
Go to the fault location and remedy the cause
of the fault.
If you cannot eliminate a fault, please contact your service provider.
Document ID: 009906_d_en_GB
to open the main menu.
(Password required)
Result
⇒
Message summary
Exit with <C>
002
Isolations
003
Information
Function
On/Off
⇒
2007-10-10 15:14:36
002 Isolations
OFF
1/01 Reception
OFF
Ground Floor
Execute
command
⇒
Select command
ON
⇒
Command response confirms the execution.
⇒
Detector or zone switched on.
⇒
LED "ISOLATION" is off, provided that there is no other
⇒
isolation.
Result
⇒
Buzzer on the station switched off.
⇒
Information on type and place of the fault.
⇒
The fault will clear automatically from the station.
Edition: 05.2009
Access level 2.1
Function
All
Zone no 2
Zone no 2
Switch to
options
extended view
(1)
(4)
(8)
LED
Test
001
002
More
4 of 4