FIRST TIME OPERATION

  
On delivery, the device is parameterized to the respective power section, and the
TAKT operating mode is set. You should review these standard parameters, and, if
necessary, adjust them for your application.
To Operate the Thyro-PX Unit for the First Time
1. Install the unit according to the installation procedures in this user manual.
The minimum connections are power, load, SETPOINT, and PULSE LOCK
jumper.
 Important
2. Turn on the system circuit breakers and apply AC input to the unit.
When the unit receives AC input, it performs self-diagnostics. If the unit detects
an error, the unit sets the respective fault bits and illuminates the FAULT LED,
or the red ON/READY LED if the fault is severe. You will not be able to apply
power to the load until you clear the fault.
3. Verify that the green ON/READY LED is lit.
4. Verify that the LIMIT LED is not lit.
5. Verify that the PULSE LOCK LED is not lit.
6. Verify that the FAULT LED is not lit.
7. Verify that an increase in setpoint applies power to the load.
If the Thyro-PX unit is delivering power and the LIMIT LED is not lit, the unit is
functioning properly.
Related Links
• "Operating Modes" on page 5-32
• "Thyro-Touch Display" on page 4-12
• "Software User Interface" on page 4-15

NORMAL OPERATION

   
Each time you turn the unit on, the unit runs a self-diagnostics procedure to ensure
that it is performing correctly. Follow the procedures in this user manual for first time
operation the first time you operate your unit. Consult the troubleshooting section if
57010148-00B
By default, the unit is configured to require a customer supplied PULSE
LOCK jumper. The unit may be customer configured to not require this
jumper.