Table 5-4. Setpoint Characteristics; Figure 5-35. Total Setpoint - Advanced Energy Thyro-PX User Manual

Power controller
Hide thumbs Also See for Thyro-PX:
Table of Contents

Advertisement

®
Advanced Energy
Analog setpoint
Bus setpoint
Motor potentiometer
Analog setpoint
Bus setpoint
Motor potentiometer
Figure 5‑35. Total setpoint
The local analog setpoint, and local motor potentiometer setpoint are used by default.
If an Anybus module is installed, the remote bus setpoint is used by default.
Switching between the local setpoint and the remote setpoint can be controlled using
the Thyro-Touch display, the Thyro-Tool Pro PC software, or the bus
communication. A digital I/O line may also be configured to control the local/remote
switch.
Table 5‑4. Setpoint characteristics
Input Type
0 mA to 20 mA
4 mA to 20 mA
0 V to 5 V
1 V to 5 V
0 V to 10 V
2 V to 10 V
57010148-00B
Setpoint configuration
Setpoint configuration
Input Characteristics
Ri = ca. 250 Ω / max. 24 mA
Ri = ca. 6.6 kΩ / max. 12 V
Ri = ca. 11.1 kΩ / max. 12 V
Installation, Setup, and Operation
Thyro-PX® Power Controller
Addition
Local
Total setpoint
Addition
Remote/local switch
Remote
Do not exceed 12 V open-
circuit
5‑34

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Thyro-px seriesThyro-px 1pxThyro-px 2pxThyro-px 3px

Table of Contents