Table 3-10. Fan Current, Air Volume, And Sound Pressure; Figure 3-1. Current Derating - Advanced Energy Thyro-PX User Manual

Power controller
Hide thumbs Also See for Thyro-PX:
Table of Contents

Advertisement

®
Advanced Energy
Table 3‑9. Current derating (Continued)
Air Temperature
45°C (113°F)
50°C (122°F)
55°C (131°F)
UL applications limited to +40°C (104°F)
Rating
Figure 3‑1. Current derating
Table 3‑10. Fan current, air volume, and sound pressure
Model
1PX
200 HF, 280 HF
300 HF, 350 HF,
495 HF, 500 HF,
650 HF
780 HF, 1000 HF,
1400 HF, 1500 HF
2000 HF, 2100 HF,
2600 HF, 2900 HF
2PX and 1PX ... VSC 2
200 HF, 280 HF
57010148-00B
Temperature (°C)
Current (A)
50 Hz
60 Hz
0.22
0.22
0.50
0.38
0.55
0.60
1.00
1.20
0.50
0.38
Specifications
Thyro-PX® Power Controller
I/I
RATED CURRENT
Self Cooling
1.00
0.95
0.88
Self cooling
Forced cooling
Air Volume
3
(m
/h)
120
150
580
2200
200
(A)
Forced Cooling
0.91
0.87
0.81
Sound Pressure
(dbA @ 1m)
53
67
75
81
67
3‑10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Thyro-px seriesThyro-px 1pxThyro-px 2pxThyro-px 3px

Table of Contents