Advanced Energy
lower load, which results in savings in investment and operating costs, and much
smaller system perturbations.
dASM can be applied whenever multiple power controllers operate together on a
common grid supply in the TAKT mode. Other features include:
• Grid load optimization for up to 32 power controllers in the TAKT mode
• Grid load optimization on the basis of power consumption of the connected
loads
• Dynamic grid load optimization, including the observance of setpoint or of the
load alterations
• Digital operation and communication
• Grid load optimization of the dASM group within up to 5 seconds
• Suitable for 1-phase or 3-phase applications
• Simple dASM wiring with shielded RJ-45 patch cables (Ethernet CAT 5 8-pole)
with a cable length between two power controllers of up to 100 m (328')
depending on surrounding conditions
• Simple parameterization for the master unit (including power limit and number
of devices)
• Monitoring the grid load (power limit)

dASM Application Considerations

When designing and installing, ensure that the:
• Electric load is evenly distributed onto the 3-phase system
• Parameterization and initiation of the individual power controller devices are in
the TAKT mode with the same TAKT cycle period (To)
• Power wiring is correct for the phases
• 1-phase and 3-phase loads are in separate dASM groups
• Power controllers and loads of a dASM group are connected to the same grid in
phase
• Shielded RJ-45 patch cables connect the dASM In and dASM Out connectors
of each unit
◦ Remove a section of the outer cable jacket to expose the shield.
◦ Place the exposed shield section of the cable under the shield clamp.
◦ Plug the RJ-45 connector into the unit.
 Important
All digital and analog control cables must be shielded. Connect the cable
shields to the shield clamp on the unit as shown in the following figure.
57010148-00B
Installation, Setup, and Operation
Thyro-PX® Power Controller
5‑39