Cooling Specifications; Table 3-8. Type Voltage 690 Volts; Table 3-9. Current Derating - Advanced Energy Thyro-PX User Manual

Power controller
Hide thumbs Also See for Thyro-PX:
Table of Contents

Advertisement

®
Advanced Energy
Table 3‑8. Type Voltage 690 Volts ... Voltage Sequence Control (VSC)
Model
Type Power
(kVA)
Type Current
(A)
Thyro-PX 1PX ... VSC2
80 H
55
200 HF
138
300 HF
207
500 HF
345
780 HF
538
1400 HF
966
1850 HF
1380
2400 HF
1794
Thyro-PX 1PX ... VSC3
80 H
55
200 HF
138
300 HF
207
500 HF
345
780 HF
538
1400 HF
966
1700 HF
1380
2200 HF
1794

COOLING SPECIFICATIONS

   
Type H Thyro-PX power controllers are self cooled, while type HF units are force
cooled. The fan in HF units require a separate power source at 230 V, 50/60 Hz.
Table 3‑9. Current derating
Air Temperature
-10°C to +25°C (14°F to 77°F)
30°C (86°F)
35°C (95°F)
40°C (104°F)
57010148-00B
Dissipation
(W)
125
260
360
625
910
1900
3200
3450
125
260
360
625
910
1900
3200
3450
Specifications
Thyro-PX® Power Controller
Current
Burden R
Transformer
(Ω)
T1
100/1
1.2
200/1
1.0
300/1
1.0
500/1
1.0
1000/1
1.2
1500/1
1.0
2000/1
1.0
3000/1
1.2
100/1
1.2
200/1
1.0
300/1
1.0
500/1
1.0
1000/1
1.2
1500/1
1.0
2000/1
1.0
3000/1
1.2
I/I
RATED CURRENT
Self Cooling
1.10
1.10
1.10
1.05
Fuse F1 (A)
100
250
350
630
2x630
4x700
4x900
4x1400
100
250
350
630
2x630
4x700
4x900
4x1400
(A)
Forced Cooling
1.10
1.05
1.00
0.96
3‑9