Electrical Specifications; Table 3-4. Electrical Specifications - Advanced Energy Thyro-PX User Manual

Power controller
Hide thumbs Also See for Thyro-PX:
Table of Contents

Advertisement

®
Advanced Energy

ELECTRICAL SPECIFICATIONS

   
Table 3‑4. Electrical specifications
Description
Electrical Requirements
AC input line voltage
Auxiliary power supply
input voltage
Fan input voltage (type
HF models)
AC line frequency
AC current
Rated power
Dissipation
Current transformer ratio
Burden Resistor
Fuse
Ground connection
Load description
External transformer
Analog inputs
Analog outputs
57010148-00B
Type voltage 500 V units: 184 V to 550 V
Type voltage 690 V units: 400 V to 759 V
90 VAC - 265 VAC (230 V 150 mA), or 24 VDC at 1 A
230 V, 50/60 Hz, for fan current and current derating see
Specifications"
on page 3-9
50/60 Hz nominal; 45 Hz to 65 Hz range
Type voltage 500 V units, see
Type voltage 500 V ... VSC, see
Type voltage 690 V units, see
Type voltage 690 V ... VSC units, see
Chassis ground near AC connector suitable for ring lug connection
Clamp for grounding the control cable shields
Resistive load (minimum 100 W)
Resistive load R
/R
warm
cold
Transformer load
The induction of the load side transformer should not exceed 1.45T
in case of mains overvoltage when using grain-oriented, cold-rolled
plates. This corresponds to a nominal induction of approximately
1.3T.
0(4) mA - 20 mA Ri = ca. 250 Ω / max. 24 mA. Max open-circuit
voltage = 24 V
0(1) V - 5 V Ri = ca. 6.6 kΩ / max. 12 V
0(2) V - 10 V Ri = ca. 11.1 kΩ / max. 12 V
Signal level 0 V - 10 V, 0 mA - 20 mA or 4 mA - 20 mA. The
maximum burden voltage is 10 V. Short-circuit proof.
Specifications
Thyro-PX® Power Controller
Specification
Table 3-5
Table 3-6
Table 3-7
Table 3-8
ratio up to 20 (MOSI starting mode)
"Cooling