Digital Inputs And Outputs - Lenze 8400 protec Hardware Manual

L-force drives
Table of Contents

Advertisement

6.6.3

Digital inputs and outputs

)
Note!
The maximum total current of the 24 V voltage supply for external actuators
and encoders is 1 A, e.g. ports
ƒ
ƒ
ƒ
Digital inputs
X41 − digital inputs DI1, DI2
Pin
Signal
1
24O
2
DI2
3
GIO
4
DI1
5
n. c.
X42 − digital inputs DI3, DI4
Pin
Signal
1
24O
2
DI4
(DO2)
3
GIO
4
DI3
(DO1)
5
n. c.
EDS84DPS424 EN 5.0
Electrical installation − HighLine/StateLine version
Digital inputs/outputs at X4x,
Analog input at X50 or SSI at X80, and
Serial interfaces RS485/RS422 at X81/X82.
Description
Type M12, 5−pole sockets
84DPSO05_5
24 V supply of the external sensors
Digital input 2
Reference potential
Digital input 1
Not assigned
Description
Type M12, 5−pole sockets
84DPSO05_5
24 V supply of the external sensors
Digital input 4
(also available as digital output)
Reference potential
Digital input 3
(also available as digital output)
Not assigned
l
Control terminals
Digital inputs and outputs
Data
According to IEC61131−2, type 1
or
Two−track frequency input for HTL
encoder 0 ... 100 kHz
HIGH
+15 .... +30 V DC
LOW
0 ... +5 V
8 mA at 24 V DC
Data
HIGH
+15 .... +30 V DC
LOW
0 ... +5 V
8 mA at 24 V DC
6
95

Advertisement

Table of Contents
loading

Table of Contents