Electrical installation − HighLine/StateLine version
Important notes

Electrical isolation

6.1.1
Electrical isolation
The protective insulation of the "8400 Inverter Drives" controllers is implemented
according to EN 61800−5−1. The following illustration shows the insulation concept.
Fig. 6−1
6.1.2

Device protection

In case of condensation, do not connect the controller to the mains voltage before
ƒ
the moisture has evaporated completely.
The controller must be protected by external fuses.
ƒ
Unused control inputs and outputs must be closed according to the intended type of
ƒ
protection.
76

X10
X10
(24 V)
X11
X11
(24 V)
X21
X21
(T1/T2)
X20
X20
(T1/T2)
Electrical isolation between power terminals, control terminals and housing
Isolation by functional insulation
I
Isolation by basic insulation
II
Safe isolation by double or reinforced insulation
Protection against accidental contact is guaranteed without any further
measures.

Power connections
X10, X11
Mains
X21
Motor
X20
Brake resistor
Control terminals
X10 (24 V)
24 V supply voltage
X11 (24 V)
X20 (T1/T2)
brake resistor temperature monitoring
X21 (T1/T2)
Motor temperature monitoring
X22
Voltage supply of external fan − only for 7.5 kW devices
X3x
Fieldbus communication
X4x
Digital inputs/outputs
X50
Analog input
X6x
Safety system
X70
Diagnostics
X80
SSI
l
X22
X6x
X80
X3x
X70
X4x
X50
E84DWPT005
EDS84DPS424 EN 5.0