6
Electrical installation − HighLine/StateLine version
Communication
PROFINET® / EtherNet/IP™
6.7.1
PROFINET® / EtherNet/IP™
Push−pull plug
X31 − fieldbus input, X32 fieldbus output
Pin
Signal
1
Tx+
2
Tx−
3
Rx+
4
res.
5
res.
6
Rx−
7
res.
8
res.
M12 plug, 4−pole
X3x − communication
Pin
Signal
1
Tx+
2
Rx+
3
Tx−
4
Rx−
6.7.2
PROFIBUS®
X3x − communication
Pin
Signal
1
P5V2
2
RxD/TxD−N
3
M5V2
4
RxD/TxD−P
5
n. c.
The station address can be set via DIP switches 1 ... 64 behind the service hatch.
100
Description
AIDA standard, type RJ45, socket, 8−pole
84DWTX0311
Transmit path + (transmit)
Transmit path − (transmit)
Receive path + (receive)
Receive path − (receive)
Description
Type M12, 4−pole, D−coded
X31 −> sockets
X32 −> sockets
84DPSO05_5
Transmit path +
Receive path +
Transmit path −
Receive path −
Description
Type M12, 5−pole, B−coded
X31 −> input −> pins
X32 −> output −> sockets
84DPSO05_5
l
Only assigned at the output
Data line A (received/transmitted data, minus)
Data ground (ground to 5 V)
Data line B (received/transmitted data, plus)
− (shield connection above the housing)
l
Data
Data
Data
5 V DC / 30 mA (bus termination)
EDS84DPS424 EN 5.0