Ingeteam Ingecon Sun 3.6TL U Installation Manual page 58

Table of Contents

Advertisement

Ingeteam Inc
Screen 1
Pout
Power (W) delivered by the inverter to the Electric Grid.
Vac
Output voltage (V) of the inverter at the Electric Grid connection.
Iac
Inverter output current (A).
Fac
Current output frequency to the Electric Grid (Hz).
PhiCos
Cosine of phi. This is the cosine of the phase angle existing between the grid voltage and the current
delivered by the inverter.
If there is no phase angle (0º), the cosine of phi is 1; cos 0º = 1.
Screen 2
Vdc
Voltage delivered by the solar panels to the inverter.
Idc
Current delivered by the solar panels to the inverter.
Screen 3
Alarm
Inverter alarm status. The installer has all the instructions for how to act for each specific alarm. Only
the alarms mentioned in this manual can be of use to the user.
0000H
0001H
0002H
0004H
0008H
0010H
0020H
0040H
0080H
0100H
0200H
0400H
0800H
1000H
2000H
4000H
8000H
The value displayed for this inverter alarm variable can be the result of the (hexadecimal) sum of two
or more of the variables listed above.
For example: alarm inverter 0006H means that the Grid Frequency and Voltage are out of range
(0002H + 0004H).
InvNum
The number assigned to the inverter through the menu that can be accessed from the display in order
to identify the communications.
Code1
The equipment operating code. It may be requested by the Ingeteam customer service.
Code2
The equipment operating code. It may be requested by the Ingeteam customer service.
SN
The serial number.
Screen 4
TotE
Total energy (kWh) delivered by the inverter to the Power grid since it was shipped from the factory. The
recording of the inverter serial number marks the start of the energy log.
T con
The number of hours that the inverter has been connected to the Power grid.
NumCon
The number of grid connections made during operating hours.
58
No alarms.
Insufficient input voltage.
Grid frequency out of range.
Grid voltage out of range.
Overcurrent at the Inverter Bridge.
Overcurrent at the DC/DC converter.
Insulation failure.
Grid overcurrent.
Over heating
Bus over voltage.
Configuration change.
Manual Stop.
HW bug.
Grid instantaneous over-current.
Detection of islanding.
Grid impedance out of range.
Hardware Failure Alert.
Installation manual
AAY2000IKI02