Ingeteam Ingecon Sun 3.6TL U Installation Manual page 39

Table of Contents

Advertisement

Installation manual
Negative pole grounded
This is the default configuration.
Negative pole has to be connected with 1 to 4 strings to A1, A2, A3 and A4 terminals, it doesn't matter the order.
Positive pole has to be connected with 1 to 4 strings to B1, B2, B3, B4 and B5 terminals. If 2 to 4 strings are used,
wires have to be connected to B1, B2, B3 and B4 terminals, it doesn't matter the order. String cannot exceed 16 A
of current each one nor 30 A together.
A1 A2 A3 A4 B1 B2 B3 B4
If only one string is used, connection will be made by B5 terminal. This terminal doesn't use the fuses that protect this
pole, so installer must provide the fuse protection of this pole complying with the provisions of the National Electrical
Code ANSI/NFPA70, Canadian Electrical Code CEC and other Local or State Codes.
A1 A2 A3 A4 B1 B2 B3 B4 B5
AAY2000IKI02
Ingeteam Inc
39

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ingecon sun 5 uIngecon sun 5tl uIngecon sun 6tl u

Table of Contents