Ingeteam Ingecon Sun 3.6TL U Installation Manual page 12

Table of Contents

Advertisement

Ingeteam Inc
AC Output
Ingecon
Sun
®
Mode
Output power factor rating
Operating frequency range
Normal output frequency
Maximum continuous output power
(AC)
Maximum output current
Maximum output fault current (AC) and
duration
Maximum output overcurrent protec-
tion
(1)
Synchronization in-rush current
Operating voltage range
Nominal output voltage (AC)
Maximum continuous output current
Mode
Must be provided by installer.
(1)
Output variables, trip limits and trip times:
Nominal frequency (Hz)
60
Nominal voltage (V)
208
240
277
Output variables accuracy:
12
3.6TL U
208
240
277
3600 W
17 A
25 A
20 A
20 A
183.04 -
211.2 -
243.76 -
228.8 V
264 V
304.7 V
208 V
240 V
277 V
17 A
15 A
13 A
208
240
277
Trip limit (Hz)
> 60.5
< 59.3
Trip limit (V)
104 (50%)
183 (88%)
228.8 (110%)
249.6 (120%)
120 (50%)
211.2 (88%)
264 (110%)
288 (120%)
138.5 (50%)
243.76 (88%)
304.7 (110%)
332.4 (120%)
Output variable
Voltage
Frequency
Time
5 U
5TL U
208
240
277
>0.99
59.7 - 60.5 Hz
60 Hz
5000 W
25 A
200 A @ 0.6 ms
35 A
30 A
25 A
5 A
183.04 -
211.2 -
243.76 -
228.8 V
264 V
304.7 V
208 V
240 V
277 V
24 A
20.83 A
18.05 A
208
240
277
Accuracy
1%
0.1 Hz
1%
Installation manual
6TL U
240
277
6000 W
26.2 A
35 A
30 A
211.2 -
243.76 -
264 V
304.7 V
240 V
277 V
25
21.66 A
240
277
Trip Times (s)
max 0.16
max 0.16
Trip Times (s)
max 0.16
max 2
max 1
max 0.16
max 0.16
max 2
max 1
max 0.16
max 0.16
max 2
max 1
max 0.16
AAY2000IKI02