Parameter Window - Automatic Control (One-Level) - ABB i-bus KNX FCL/S 1.6.1.1 Product Manual

Blower actuator, fcl/s x.6.1.1 series
Table of Contents

Advertisement

®
ABB i-bus
KNX
Start-up
3.2.2.3.2

Parameter window - Automatic control (One-level)

This parameter window is visible if the Enable automatic operation parameter in
A: Fan
This is the parameter window where you define the threshold values for switchover of the fan speed. You
can also enable limitations here.
Object value "Automatic On/Off"
switch on to the automatic
Options:
This parameter defines how the device should react to a telegram.
1: Automatic is activated by a telegram with value 1.
0: Automatic is activated by a telegram with value 0.
Threshold value OFF <-> ON
in % [1...100]
Options:
This defines the threshold value at which switch on occurs. If the value in the control value communication
object is greater than or equal to the parameterized threshold value, it is switched on. If the value is less, it
is switched off.
(One-level), p.44 is set to Yes.
1
0
1...10...100
Parameter window -
FCL/S x.6.1.1 | 2CDC508116D0203 49