Parameter Window - Direct Operation - ABB i-bus KNX FCL/S 1.6.1.1 Product Manual

Blower actuator, fcl/s x.6.1.1 series
Table of Contents

Advertisement

®
ABB i-bus
KNX
Start-up
3.2.2.1.3

Parameter window - Direct operation

This parameter window is visible if the Enable direct operation parameter in
(Multi-level), p.21 is set to Yes.
Enable communication objects
"Switch speed x" 1 bit
Options:
Yes: Three 1 bit communication objects, Switch speed x (x = 1...3) are enabled.
The device receives a setting telegram via these communication objects.
Telegram value
If several ON/OFF telegrams are received consecutively in a short period of time at various Fan speed
1...3 communication objects, the value last received will be the one used to control the fan. An OFF tele-
gram to one of the three communication objects Fan speed 1...3 switches the fan off.
Important
Forced operation remains valid and is taken into account.
The parameterized minimum fan speed dwell time for automatic operation is ignored during manual
operation. Accordingly, an immediate reaction to manual operation is detected.
The delay time with speed switchover remains active to protect the fan.
38 2CDC508116D0203 | FCL/S x.6.1.1
No
Yes
1 = Fan speed x is switched on
0 = fan speed x is switched off
Parameter window A: Fan