Direct Operation; Switchover Between Automatic And Direct Operation - ABB i-bus KNX FCL/S 1.6.1.1 Product Manual

Blower actuator, fcl/s x.6.1.1 series
Table of Contents

Advertisement

®
ABB i-bus
KNX
Planning and application
4.1.3

Direct operation

With direct fan control via the ABB i-bus
three floating contacts. A single-speed, two-speed or three-speed fan can be connected.
The device sets the fan speed in accordance with a value received via the ABB i-bus
ceived as a 1 byte value.
1 byte value
4.1.4

Switchover between automatic and direct operation

The device can switch between automatic operation and direct operation. The changeover to manual fan
control is implemented via a 1 bit value. The fan speed is switched in accordance with the 1 byte value re-
ceived.
Fan control is changed back to automatic operation if a 1 is received on the respective communication ob-
ject.
The current status of automatic operation is fed-back via a 1 bit value.
86 2CDC508116D0203 | FCL/S x.6.1.1
Hexadecimal
0
00
1
01
2
02
3
03
>3
>03
®
, a fan drive is connected directly to the device and switched via
Binary value bit
76543210
00000000
0 (OFF)
00000001
Fan speed 1
00000010
Fan speed 2
00000011
Fan speed 3
>00000011
Values greater than 3 are ignored
®
. The value is re-
Fan speed

Advertisement

Table of Contents
loading

This manual is also suitable for:

I-bus knx fcl/s 2.6.1.1

Table of Contents