ABB i-bus
KNX
Start-up
3.2.2.2

Parameter window A: Fan (Two-level)

All settings for output A are made in this parameter window.
These explanations also apply to outputs C, D, E if the parameter Outputs C, D, E in
Enable outputs
All settings for the two-speed fan are made in this parameter window.
If you wish to use the device for controlling a two-speed fan, set the parameters as follows:
In the A: Fan parameter window, select the multi-level option in the Fan type parameter.
Select Yes in the Limit fan speeds to 2 parameter.
Now a two-speed fan is controlled via fan speeds 1 and 2.
Fan speed 3 with all its parameters and options is now non-functional.
Note
Further parameters and their settings options are described in parameter window
A: Fan
A...F, p.20 is set to Enable as fans.
(Multi-level), p.21.
Parameter window
Parameter window