Universal IV™ CM Density Compensated Model
Section 6:
6.1
General safety information
This document contains installation instructions for potentially explosive atmosphere
applications.
The Universal U IV CM Denisty Compensation System is approved for use in
hazardous locations when properly installed. Control drawings detailing installation
guidelines are available in Section 6.4.
Always Install to Local Codes / Requirements / Directives as Mandated by the
Authority Having Jurisdiction.
The aluminum enclosure must be protected from mechanical friction and impact
that could cause ignition capable sparks.

6.1.1 Warning

• Installation, Start-Up, and Service should only be performed by personnel
• Substitution of Components May Impair Intrinsic Safety.

6.1.2 Device Description

Each AMETEK Drexelbrook Universal IV CM-DC system consists of a
Density Compensation unit
- Power - four-wire
- HART 7.0 4-20 mA
- Modbus
UIV CM Water Cut RF Admittance transmitter
-with a 700 series sensing element
Capacitance is transmitted to the DCM from a UIV CM via HART 5.0.
Required density, temperature and flow rate data are transmitted to the DCM via
Modbus from an external source such as a Coriolis meter.
Configuration and calibration of the DCM is accomplished via the onboard keypad
and LCD display
Or
Remotely by a PC running STExplorer T.M. software with a HART modem
Hazardous Location Approval Supplementary Installation
& Operating Instructions
trained in explosive atmosphere installations.