BESTCOMSPlus voltage protection settings (DGC-2020, Generator Protection, Voltage, Overvoltage) are
illustrated in Figure 4-32. The 59-1 element is shown.
A
Pickup: Adjustable from 70 to 576 Vac in 1 Vac increments.
B
Activation Delay: Adjustable from 0 to 30 s in 0.1 s increments.
C
Alarm Configuration: None, Alarm, or Prealarm.
D
Hysteresis: Adjustable from 1 to 60 Vac in 1 Vac increments.
E
Low Line Scale Factor: Adjustable from 0 to 3.000 in increments of 0.001.
Phase Imbalance (47)
DGC-2020 controllers with enhanced generator protection (style number xxxxxxExx) are capable of
protecting against voltage imbalances between any of the three phases. The pickup setting entered is
based on the VT secondary side (DGC-2020). A phase imbalance condition is annunciated when the
difference between any of the three phases of generator voltage increases above the 47 pickup setting
for the duration of the 47 activation delay setting
C
to trigger a pre-alarm
(warning) or alarm
user-configured to close a programmable output.
D
The hysteresis setting
functions as a phase imbalance dropout by preventing rapid switching of the
pickup output.
BESTCOMSPlus voltage protection settings (DGC-2020, Generator Protection, Voltage, Phase
Imbalance) are illustrated in Figure 4-32.
A
Pickup: Adjustable from 5 to 100 Vac in 1 Vac increments.
B
Activation Delay: Adjustable from 0 to 30 s in 0.1 s increments.
C
Alarm Configuration: None, Alarm, or Prealarm.
D
Hysteresis: Adjustable from 1 to 5 Vac in 1 Vac increments.
9400200990 Rev I
Figure 4-31. Overvoltage Protection Settings
B
. A phase imbalance annunciation can be user-selected
C
(shutdown). A phase imbalance annunciation can also be
Figure 4-32. Phase Imbalance Protection Settings
DGC-2020 BESTCOMSPlus Software
A
4-35