Operating Power
The LSM-2020 operating power input accepts either 12 Vdc or 24 Vdc and tolerates voltage over the
range of 6 to 32 Vdc. Operating power must be of the correct polarity. Although reverse polarity will not
cause damage, the LSM-2020 will not operate. Operating power terminals are listed in Table 8-1.
It is recommended that a fuse be added for additional protection for the wiring to the battery input of the
LSM-2020. A Bussmann ABC-7 fuse or equivalent is recommended.
Terminal
P2-1 (CHASSIS)
P2-2 (BATT+)
P2-3 (BATT–)
Analog Outputs
The LSM-2020 has three sets of analog output contacts: AVR control, GOV control, and Load Share Line.
The AVR control output contacts provide remote control of the generator voltage setpoint. The GOV
control output contacts provide remote control of the generator speed (RPM) setpoint. The generator
uses the measured LS (Load Share Line) output to calculate the per unitized average load level, and
uses that as the set point for its kW controller. Analog input terminals are listed in Table 8-2.
Terminal
P2-18 (AVR+)
P2-17 (AVR–)
P2-16 (AVR')
P2-15 (GOV+)
P2-14 (GOV–)
P2-13 (GOV')
P2-6 (LS+)
P2-5 (LS–)
P2-4 (LS')
Analog Inputs
These inputs do not have functionality at this time. They are for future enhancement. Analog input
terminals are listed in Table 8-3.
Terminal
P2-9 (V+)
P2-8 (IN–)
P2-7 (I+)
9400200990 Rev I
Table 8-1. Operating Power Terminals
Chassis ground connection
Positive side of operating power input
Negative side of operating power input
Table 8-2. Analog Output Terminals
AVR control output positive
AVR control output negative
Provides additional landing point for external resistor
GOV control output positive
GOV control output negative
Provides additional landing point for external resistor
Load share line positive
Load share line negative
Provides additional landing point for external resistor
Table 8-3. Analog Input Terminals
Future enhancement.
Future enhancement.
Future enhancement.
DGC-2020 LSM-2020 (Load Share Module)
Description
Description
Description
8-7