Parameter
Register
40001-18
RESERVED
PARAMETER SETTINGS
40019
Emergency Stop
40020
Remote Start / Stop
40021-22
RESERVED
SYSTEM PARAMETERS
40023
Default Generator Connection
40024
NFPA Level
40025
RESERVED
40026
Rated Engine RPM
40027
Number Flywheel Teeth
40028
Genset KW Rating
40029
No Load Cool Down Time
GENERATOR PT PRIMARY
40030
Voltage(a)
40031
Voltage(b)
GENERATOR PT SECONDARY
40032
Voltage
GENERATOR CT PRIMARY
40033
Current
LOW FUEL ALARM
40034
Enable
40035
Threshold
LOW FUEL PRE-ALARM
40036
Enable
40037
Threshold
LOW COOLANT TEMP PRE-ALARM
40038
Enable
40039
Threshold
BATTERY OVERVOLTAGE PRE-ALARM
40040
Enable
40041
RESERVED
MAINTENANCE INTERVAL PRE-ALARM
40042
Enable
40043
Threshold
ENGINE KW OVERLOAD PRE-ALARM
40044
Enable
40045
Threshold
HIGH COOLANT TEMP PRE-ALARM
40046
Enable
40047
Threshold
LOW OIL PRESSURE PRE-ALARM
40048
Enable
9400200990 Rev I
Table B-3. Legacy Parameter Table
Range
0-1
0-1
0-2
0-2
750-3600
50-500
25-9999
0-60
1-15000
1-480
1-5000
0-1
2-50
0-1
10-100
0-1
32-150
0-1
0-1
0-5000
0-1
95-140
0-1
100-280
0-1
DGC-2020 Modbus™ Communication
Read/Write
Data
Supported
Format
0 =Off
W
1 =Stop
0 =Stop
W
1 =Start
0=3ph L-L
R W
1=3ph L-N
2=1ph A-B
0=Off
R W
1=Level 1
2=Level 2
R W
R W
R W
R W
R W
DP
R W
DP
R W
R W
0 =Off
R W
1 =On
R W
0 =Off
R W
1 =On
R W
0 =Off
R W
1 =On
R W
0 =Off
R W
1 =On
0 =Off
R W
1 =On
R W
0 =Off
R W
1 =On
R W
0 =Off
R W
1 =On
R W
0 =Off
R W
1 =On
Units
RPM
KWatt
Minutes
VoltsAC x10000
VoltsAC
VoltsAC
AmpsAC
% Full Tank
% Full Tank
Degrees F
Hours
% of Rated
Degrees F