Basler DGC-2020 Instruction Manual page 140

Digital genset controller
Table of Contents

Advertisement

Name
TRUE when the 59-2 overvoltage is in a TRIP condition. Connect to
59-2TRIP
another logic block input.
TRUE when the 81 frequency is in a TRIP condition. Connect to
81TRIP
another logic block input.
Other Element Objects
When this input is TRUE, and the DGC-2020 is in OFF mode, the
AUTOMODE
DGC-2020 will switch to AUTO mode. This is a pulsed input. It does
not need to be held after the desired mode switch has occurred.
Can be connected to inputs of other logic blocks. When the AVR is
AVR
being raised, the Raise output is TRUE. When being lowered, the
Lower output is TRUE.
Eight configurable elements can be set up on the Configurable
Elements screen using the Settings Explorer. A configurable element
CONFELMNT
can be programmed to annunciate an alarm or pre-alarm when the
input is TRUE.
Used to control the generator breaker. Connect the inputs and outputs
GENBRK
to inputs and outputs of other logic blocks.
Can be connected to inputs of other logic blocks. When the Governor is
GOVR
being raised, the Raise output is TRUE. When being lowered, the
Lower output is TRUE.
LOGICALM
When this input is TRUE, the DGC-2020 goes into an Alarm condition.
When this input is TRUE, the DGC-2020 goes into a Pre-alarm
LOGICPALM
condition.
5-10
Description
DGC-2020 BESTlogic+ Programmable
Symbol
9400200990 Rev I