Basler DGC-2020 Instruction Manual page 74

Digital genset controller
Table of Contents

Advertisement

The Low Line Scale Factor setting
applications that may utilize more than one type of genset connections. The scale factor setting is
implemented when the DGC-2020 senses a contact closure at a contact input programmed to activate
scaling of the settings. The value of the scale factor setting serves as a multiplier for the threshold
settings. For example, if a scale factor contact input is received bye the DGC-2020 and the scale factor
setting is 2.000, the threshold setting will be doubled (2.000 x PU).
Measurement/Metering Units
The user can configure the DGC-2020 to display and report engine oil pressure and coolant temperature
in English or metric units of measure
Battery Voltage
M
The nominal voltage
of the starter battery is used by the DGC-2020 to detect and annunciate battery
overvoltage and low or weak battery voltage.
NFPA Compliance Level
The DGC-2020 can be used in an application requiring compliance with NFPA Standard 110. Levels 1
and 2 of Standard 110 are supported
ways:
The number of crank cycles is fixed at 3
Crank cycle time is fixed at 15 seconds
Continuous crank time is fixed at 45 seconds
The low coolant temperature pre-alarm setting is fixed at 70°F
Horn
An output contact configured (through programmable logic) to energize a horn
disabled through BESTCOMSPlus or at the DGC-2020 front panel.
Single-Phase Override
The DGC-2020 will switch to single-phase voltage sensing
single-phase override input) is received. Either A-to-B or A-to-C sensing can be selected.
Fuel Level Function
Q
This setting
allows the selection of four fuel types: Fuel Lvl, Natural Gas, Liquid Propane, or Disabled.
Selecting a fuel type other than Fuel Lvl will disable any fuel level indication, alarm, and pre-alarm and
disable the Fuel Level value on the Engine screen of the Metering Explorer in BESTCOMSPlus.
Load Sharing Module
R
A J1939 Address
must be entered when an optional LSM-2020 is enabled
Power Up Delay
In some cases, the ECO takes longer than the DGC-2020 to power up. The power up delay setting
used to delay the initial pulsing of the ECU for data on DGC-2020 power up.
Contact Expansion Module
U
A J1939 Address
must be entered when the optional CEM-2020 is enabled
BESTCOMSPlus system settings (DGC-2020, System Parameters, System Settings) are illustrated in
Figure 4-16.
4-18
K
is used to automatically adjust the EPS threshold settings in
L
.
N
. Selecting level 1 or 2 affects DGC-2020 operation in the following
DGC-2020 BESTCOMSPlus Software
O
can be enabled and
P
when a contact input (programmed as a
S
.
V
.
T
is