Basler DGC-2020 Instruction Manual page 135

Digital genset controller
Table of Contents

Advertisement

Name
Global Alarm
TRUE when one or more Alarms are set.
TRUE when one or more of the Sender Fails are
Global Sender Fail
configured as Alarms and are TRUE.
TRUE when the High Coolant Temp Alarm settings have
Hi Coolant Temp
been exceeded.
TRUE when the Low Coolant Level function is
configured as an Alarm and the activation delay has
Low Coolant Level
expired. In addition, TRUE when Canbus is enabled and
the Low Coolant Level Alarm threshold has been
exceeded.
TRUE when the Low Fuel Level Alarm settings have
Low Fuel Level
been exceeded.
TRUE when the Low Oil Pressure Alarm settings have
Low Oil Pressure
been exceeded.
Oil Pressure
TRUE when the Oil Pressure Sender Fail is configured
Sender Fail
as an Alarm and the activation delay has expired.
Overcrank
TRUE when an Overcrank condition exists.
TRUE when the Overspeed Alarm settings have been
Overspeed
exceeded.
TRUE when the Speed Sender Fail activation delay has
Speed Sender Fail
expired.
Voltage Sensing
TRUE when the Voltage Sensing Fail is configured as an
Fail
Alarm and the activation delay has expired.
Pre-Alarms
TRUE when the Battery Charger Fail function is
Battery Charger
configured as a Pre-Alarm and the activation delay has
Fail
expired.
Battery
TRUE when the Battery Overvoltage Pre-Alarm
Overvoltage
threshold has been exceeded.
Contact Expansion
TRUE when communication from the CEM-2020 to the
Module Comm Fail
DGC-2020 has been lost.
Coolant Temp
TRUE when the Coolant Temp Sender Fail is configured
Sender Fail
as a Pre-Alarm and the activation delay has expired.
Diag Trouble Code
TRUE when a Diagnostic Trouble Code exists.
ECU Com Loss
TRUE when communication to ECU has been lost.
9400200990 Rev I
Description
DGC-2020 BESTlogic+ Programmable Logic
Symbol
5-5