Basler DGC-2020 Instruction Manual page 229

Digital genset controller
Table of Contents

Advertisement

Holding
Parameter
Register
Embedded Code Version Number
40281
(a)
Embedded Code Version Number
40282
(b)
Embedded Code Version Number
40283
(c)
40287-97
RESERVED
Read Relay Image of both Main
40298
and Aux Output
40299
RESERVED
J1939 DIAGNOSTIC TROUBLE CODES
Active DTC Number 16 – Lower
40300
Two Bytes
Active DTC Number 16 – Upper
40301
Two Bytes
Active DTC Number 15 – Lower
40302
Two Bytes
Active DTC Number 15 – Upper
40303
Two Bytes
Active DTC Number 14 – Lower
40304
Two Bytes
Active DTC Number 14 – Upper
40305
Two Bytes
Active DTC Number 13 – Lower
40306
Two Bytes
Active DTC Number 13 – Upper
40307
Two Bytes
Active DTC Number 12 – Lower
40308
Two Bytes
Active DTC Number 12 – Upper
40309
Two Bytes
Active DTC Number 11 – Lower
40310
Two Bytes
Active DTC Number 11 – Upper
40311
Two Bytes
Active DTC Number 10 – Lower
40312
Two Bytes
Active DTC Number 10 – Upper
40313
Two Bytes
Active DTC Number 9 – Lower
40314
Two Bytes
Active DTC Number 9 – Upper
40315
Two Bytes
Active DTC Number 8 – Lower
40316
Two Bytes
Active DTC Number 8 – Upper
40317
Two Bytes
Active DTC Number 7 – Lower
40318
Two Bytes
9400200990 Rev I
Range
0-99
0-9999
0-9999
individual bits
are 0 or 1
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
DGC-2020 Modbus™ Communication
Read/Write
Data
Supported
Format
R
R
R
Main is in lower byte and Aux is in
upper byte.
b0 = Aux Output 1,
b1 = Aux Output 2,
b2 = Aux Output 3,
b3 = Aux Output 4,
b4 = Aux Output 5,
b5 = Aux Output 6,
b6 = Aux Output 7,
R
b7 = Aux Output 8.
b8 = Master Start Relay,
b9 = Fuel Solenoid Relay,
b10 = PreHeat PreLube Relay,
b11 = Alarm Relay,
b12 = UNASSIGNED,
b13 = Buzzer On,
b14 = EPS Loaded Relay,
b15 = PreAlarm Relay,
Half of a set of DTC data as defined in
R
SAE J1939-73
Half of a set of DTC data as defined in
R
SAE J1939-73
Half of a set of DTC data as defined in
R
SAE J1939-73
Half of a set of DTC data as defined in
R
SAE J1939-73
Half of a set of DTC data as defined in
R
SAE J1939-73
Half of a set of DTC data as defined in
R
SAE J1939-73
Half of a set of DTC data as defined in
R
SAE J1939-73
Half of a set of DTC data as defined in
R
SAE J1939-73
Half of a set of DTC data as defined in
R
SAE J1939-73
Half of a set of DTC data as defined in
R
SAE J1939-73
Half of a set of DTC data as defined in
R
SAE J1939-73
Half of a set of DTC data as defined in
R
SAE J1939-73
Half of a set of DTC data as defined in
R
SAE J1939-73
Half of a set of DTC data as defined in
R
SAE J1939-73
Half of a set of DTC data as defined in
R
SAE J1939-73
Half of a set of DTC data as defined in
R
SAE J1939-73
Half of a set of DTC data as defined in
R
SAE J1939-73
Half of a set of DTC data as defined in
R
SAE J1939-73
Half of a set of DTC data as defined in
R
SAE J1939-73
Units