Name
Engine KW Over
TRUE when the Engine KW Overload 1 Pre-Alarm
Load 1
settings have been exceeded.
Engine KW Over
TRUE when the Engine KW Overload 2 Pre-Alarm
Load 2
settings have been exceeded.
Engine KW Over
TRUE when the Engine KW Overload 3 Pre-Alarm
Load 3
settings have been exceeded.
TRUE when the Fuel Leak Detect function is configured
Fuel Leak
as a Pre-Alarm and the activation delay has expired.
Fuel Level Sender
TRUE when the Fuel Level Sender Fail is configured as
Fail
a Pre-Alarm and the activation delay has expired.
Global Pre-Alarm
TRUE when one or more Pre-Alarms are set.
TRUE when the High Coolant Temp Pre-Alarm threshold
Hi Coolant Temp
has been exceeded.
TRUE when the High Fuel Level Pre-Alarm settings
High Fuel Level
have been exceeded.
TRUE when an individual generator detects that it had
Intergenset Comm
been connected to a generator network, but has lost the
Fail
connection.
Load Share
TRUE when communication from the LSM-2020 to the
Module Comm Fail
DGC-2020 has been lost.
Low Battery
TRUE when the Low Battery Voltage Pre-Alarm settings
Voltage
have been exceeded.
TRUE when the Low Coolant Level function is
configured as a Pre-Alarm and the activation delay has
Low Coolant Level
expired. In addition, TRUE when Canbus is enabled and
the Low Coolant Level Pre-Alarm threshold has been
exceeded.
TRUE when the Low Coolant Temp Pre-Alarm threshold
Low Coolant Temp
has been exceeded.
TRUE when the Low Fuel Level Pre-Alarm threshold has
Low Fuel Level
been exceeded.
TRUE when the Low Oil Pressure Pre-Alarm threshold
Low Oil Pressure
has been exceeded.
Maintenance
TRUE when the Maintenance Interval Pre-Alarm
Interval
threshold has been exceeded.
MPU Fail
TRUE when the MPU has failed.
Multiple Contact
Expansion
TRUE when more than one CEM-2020 is connected.
Modules Detected