3 Programming
will ignore the message. The resulting retransmissions of messages will
slow communications on the network.
If this value is set too long, the drive will wait longer than necessary to
determine that the message is completed. This will delay the drive's re-

3.9 Parameter Group 6-** Technical Functions

3
600-605 Operating Data
Value:
Par. no.
Description
600
Operating hours
601
Hours run
602
kWh counter
603
Number of power-up's
604
Number of overtemperatures
605
Number of overvoltages
Function:
These parameters can be read out via the serial communication port and
the LCP control unit.
Description of choice:
Parameter 600, Operating hours:
Gives the number of hours the frequency converter has been operating.
The value is saved every hour and when there is a mains failure. This
value cannot be reset.
Parameter 601, Hours run:
Gives the number of hours the motor has been operating since the reset
Reset of hours-run counter
in parameter 619
hour and when there is a mains failure.
Parameter 602, kWh counter:
Gives the frequency converter's output energy in kWh. The calculation is
based on the mean kW value over one hour. This value can be reset using
Reset of kWh counter
parameter 618
Range: 0 - depends on unit.
Parameter 603, Number of power-ups:
Gives the number of power-ups of the supply voltage undertaken on the
frequency converter.
Parameter 604, Number of overtemperatures:
Gives the number of overtemperature faults that have been registered on
the frequency converter's heat sink.
Parameter 605, Number of overvoltages:
Gives the number of overvoltages of the intermediate circuit voltage in
the frequency converter. This is only counted when Alarm 7
is active.
NB!
Parameters 615-617
the integral control unit.
615
Fault log: Error code
Value:
[Index 1 - 10] Error code: 0 - 99
Function:
In this parameter it is possible to see the reason for a trip (cut-out of the
frequency converter) occurring. 10 [1-10] log values are defined.
The lowest log number [1] contains the latest/most recently saved data
value. The highest log number [10] contains the oldest data value saved.
84
Display text
(OPERATING HOURS)
(RUNNING HOURS)
(KWH COUNTER)
(POWER UP'S)
(OVER TEMP'S)
(OVER VOLT'S)
. The value is saved every
.
Overvoltage
Fault log
cannot be read out via
MG.04.B8.02 - VLT is a registered Danfoss trademark
sponse to the message and possibly cause the master controller to time
out. The resulting retransmissions of messages will slow communications
on the network.
Unit
Hours
Hours
kWh
Number of times
Number of times
Number of times
If a trip occurs, it is possible to see the cause, time and a possible value
of the output current or output voltage.
Description of choice:
Given as a fault code, in which the number refers to a table. See the table
Warnings/alarm messages
in
.
616
Fault log: Time
Value:
[Index 1 - 10] Hours: 0 - 130,000.0
Function:
In this parameter it is possible to see the total number of operating hours
in connection with the last 10 trips.
10 [1-10] log values are denoted. The lowest log number [1] contains the
latest/most recently saved data value, and the highest log number [10]
contains the oldest data value.
Description of choice:
Read out as one value.
617
Fault log: Value
Value:
[Index 1 - 10] Value: 0 - 9999
Function:
In this parameter it is possible to see at which value a trip occurred. The
unit of the value depends on which alarm is active in parameter 615
log: Fault code
.
Description of choice:
Read out as one value.
618
Reset of kWh counter
Value:
No reset (DO NOT RESET)
Reset (RESET COUNTER)
Function:
kWh counter
Resetting parameter 602
Description of choice:
Reset
If
[1]is selected and you press the [OK] key, the frequency con-
verter's kWh counter is reset to zero. This parameter cannot be selected
via serial communication.
VLT® Decentral FCD
Range
0-130,000.0
0-130,000.0
Depends on unit
0-9999
0-9999
0-9999
Fault
[0]
[1]
to zero.

Advertisement

Table of Contents
loading

Table of Contents