Section 4
Starting up
4.6
40
IEC13000062 V1 EN-US
Figure 7:
Select: Use the following IP address
6.
Use the ping command to verify connectivity with the IED.
7.
Close all open windows and start PCM600.
The PC and IED must belong to the same subnetwork for this set-
up to work.
Setting up the PC to access the IED via a network
The same method is used as for connecting to the front port.
The PC and IED must belong to the same subnetwork for this set-
up to work.

Writing an application configuration to the IED

When writing a configuration to the IED with PCM600, the IED is automatically
set in configuration mode. When the IED is set in configuration mode, all functions
are blocked. The red LED on the IED flashes, and the green LED is lit while the
IED is in the configuration mode.
IEC13000062-1-en.vsd
Railway application RER670 2.2 IEC
1MRK 506 377-UEN C
M11734-2 v7
Commissioning manual