2YHUYLHZ
This section describes the Presignal and PAS selection, how to do the following:
•
View Presignal and PAS selections,
•
Respond to an alarm with Presignal
•
Operate the control panel with a Presignal Delay Timer only
•
Operate the control panel with a Presignal Delay Timer and PAS
:KDWLV3UHVLJQDODQG3$6"
Presignal is a feature that initially causes alarm signals to only sound in specific areas,
monitored by qualified persons, where activating a general alarm requires human
verification. This allows delay of the alarm up to 180 seconds after the start of alarm
processing. The control panel Presignal feature provides two selections:
•
A Presignal Delay Timer (60-180 seconds) that delays activation of all outputs
with a CBE that includes Special Zone F0.
•
A PAS selection, in addition to the Presignal Delay Timer, that allows a
15-second time period for acknowledging an alarm signal from a fire detection/
initiating device. If the alarm is not acknowledged within 15 seconds, all local and
remote outputs activate immediately and automatically.
Figure 80 contains an illustration of Presignal and PAS timing.
3$6 V
,I 3$6
RXWSXWV LI QRW DFNQRZOHGJHG
,QLWLDO DODUP
DQQXQFLDWLRQ
)LJXUH 3UHVLJQDO DQG 3$6 7LPH
Presignal and Positive Alarm Sequence (PAS) Operation
3UHVLJQDO 'HOD\ 7LPHU V
< DODUP DFWLYDWHV
AFC-600 Operations PN 51033:A 3/8/99
$ODUP DFWLYDWHV RXWSXWV LI
SDQHO LV QRW UHVHW
Continued on the next page...