3XUSRVHRI5HOHDVLQJ=RQHV
The control panel provides ten Releasing Zones (R0-R9). Zones R0–R9 are special
zones that you can use for up to ten independent releasing operations. This section
contains descriptions of each Releasing Function option and a example of how
Releasing Zones options work (refer to "How Releasing Zones Operate" on page 73).
For instructions on programming Releasing Functions, refer to the AFC-600
Programming Manual. Each Releasing Zone includes the following releasing options:
Option
Description
Cross Zone
Cross Zones let you program the control panel to activate a Releasing
Zone when two or more detectors are alarmed. Cross Zone selections
are:
Y Two or more detectors are alarmed that are mapped to one of the ten

Releasing Zones (R0-R9)

Z Two or more detectors are alarmed that are mapped to two different
Software Zones and mapped to one of the ten Releasing Zones (R0-R9).
H At least one smoke detector mapped to one of the ten Releasing
Zones (R0-R9) is alarmed and at least one heat detector mapped to one
of the ten Releasing Zones (R0-R9) is alarmed.
N Cross Zones not used
Delay Timer
Select a 0–60 second delay before activating a zone.
Abort
An Abort Switch Type Code used to abort activation of a zone.
Manual Release
Allows immediate zone activation by overriding the abort function,
cross-zone function, and delay timer.
Soak Timer
Automatically shuts off the releasing device. Select 0001-9999 seconds
for a Soak Timer or 0000 seconds for no Soak Timer.
+RZWR9LHZ5HOHDVLQJ=RQH6HOHFWLRQV
You can use the Read Status Entry option to view the current selections for a Releasing
Zone. For example, to view selections for Releasing Zone R1, press the keys in
sequence:
&&]U&
Figure 74 shows a sample LCD display of a Releasing Function selected for Releasing
Zone R1:
2)) 5(/($6( )81&7
'(/$<  $%257 8/, &5266 1 62.  5
)LJXUH  6DPSOH 5HDG 6WDWXV IRU D 5HOHDVLQJ =RQH
7DEOH  5HOHDVLQJ 2SWLRQV
6WDWXV 2Q RU 2II
5HOHDVLQJ )XQFWLRQ VWDWXV EDQQHU
5(/($6( &21752/
$ERUW )XQFWLRQ VHOHFWLRQ IRU
WKH 5HOHDVLQJ =RQH
AFC-600 Operations PN 51033:A 3/8/99
Releasing Zones (R0-R9)
5HOHDVLQJ =RQH 5
Continued on the next page...