Alarm Operation; Supervisory Operation; Nac (Notification Appliance Circuit) Operation - Notifier AFP-100 Instruction Manual

Intelligent fire panel
Table of Contents

Advertisement

4. Operation

Alarm Operation

Alarm operation is similar to trouble operation, but with the following differences:
A typical alarm display would be:

Supervisory Operation

Supervisory operation is similar to alarm operation but with the following differences:
A typical supervisory event would display:
Note that, like alarms, supervisory signals latch and can be assigned to a software zone. Supervisory
alarms do not cause resound as do other alarm conditions. Open circuits in supervisory wiring are
processed by the control panel the same way as other trouble conditions.

NAC (Notification Appliance Circuit) Operation

The control panel has two NACs: NAC 01 and NAC 02.
NAC 01 and NAC 02 are programmable. Both NACs may be either silenceable or nonsilenceable and
may be programmed as steady or coded operations. Coded operation includes March Time, Temporal or
California types. Refer to "Coded Operation - NAC 01 and NAC 02" on page 66, for additional
information on coding.
64
Technical Manuals Online! - http://www.tech-man.com
• The panel sounder produces a steady output, not pulsed.
• The System Alarm (not Trouble) LED flashes.
• ALARM: device name, type and address are displayed.
• Alarms latch and are not allowed to clear automatically.
• Alarms activate software zones (control-by-event logic) if so programmed.
• Timers (Silence Inhibit, Auto-silence, Trouble Reminder) are started.
• Alarms activate the general alarm relay and zone Z00 (NAC 01 and NAC 02).
• The trouble relay is not activated.
ALARM: PULL STAT M02
<ADJ><NOUN> ZONE #
• The panel sounder is a warbling sound.
• The Supervisory LED (not Alarm) flashes.
• The Display Status label is Active.
• Supervisory relay is activated.
• Silenced alarms are not resounded.
• Timers are not started.
• The alarm relay is not activated.
ACTIVE TAMPER M02
<ADJ><NOUN> ZONE #
Alarm Operation
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afp-100e