The system operates in Normal mode when no alarms or troubles exist. In Normal
mode, the control panel displays a system message as follows:
$// 6<67(06 1250$/ $ 78( 
)LJXUH  6DPSOH $OO 6\VWHPV 1RUPDO 0HVVDJH
In Normal mode, the control panel does the following functions at regular intervals:
Polls all SLC devices, Panel Circuits, and the four NACs to check for valid replies,
alarms, troubles, circuit integrity, and supervisory signals, and so forth
Checks power supply troubles and batteries at 10-second intervals
Sends a supervisory query on the optional terminal mode LCD-80 and verifies
proper response
Refreshes the LCD display and the optional terminal mode LCD-80 display and
updates time
Scans for any keypad or Control Key entries
Performs a detector automatic test operation
Tests system memory