cOOLANT TeMPerATUre AND MOISTUre cONDeNSATION
Temperature control
The cooling can be switched on by means of a pneumatic valve or a solenoid valve,
which is connected uptream by a relay. The valves for temperature control must be used
in the flow line of the cooling circuit in order to avoid pressure surges. All conventional
valves can be used. Make sure that the valves are working properly and do not clamp.
ATTENTION
Destruction of the heat sink at storage of water-cooled devices!
Observe the following points when storing water-cooled devices
► Completely empty the cooling circuit
► Blow out the cooling circuit with compressed air