cONNecTION OF THe POWer UNIT
4.2.3 Ac connection
4.2.3.1 AC supply 400 V / 3-phase
L1
L2
L3
PE
No.
Typ
Mains voltage
①
Mains form
Personal protection
②
Mains fuses
③
Mains contactor
④
Mains choke
HF filter for TN-, TT
⑤
systems
HF filter for IT systems
⑥
KEB COMBIVERT
Figure 16:
Connection of the mains supply 400 Vac / 3-phase
4.2.3.2 Supply line
The conductor cross-section of the supply line is determined by the following factors:
• input current of the drive converter
• used cable type / installation and ambient temperatures
• applicable local electrical regulations
PE
PE
TN, TT
The rated voltage between one phase conductor and earth potential (or arti-
ficial neutral point in the IT mains) must not exceed 300 V (effective value).
RCMA with separator or RCD type B
Required for compliance with the limit values in accordance with
The application engineer is responsible for the design!
L1
L2
L3
PE
Description
3-phase 400 Vac
Type gG or MCCB
see notes under the table
3.
F6
U
V
W
PE
IT
Earth leakage monitor
EN 61800-
49