Control Cabinet Installation; Figure 8: Mounting Distances; Figure 9: Control Cabinet Ventilation - KEB COMBIVERT F6 Instructions For Use Manual

Installation f6 housing 6
Hide thumbs Also See for COMBIVERT F6:
Table of Contents

Advertisement

DIMeNSIONS AND WeIGHTS

3.3.5 control cabinet installation

Power loss for the control cabinet dimension
depending on the operating mode/load.
Mounting distances
A
D
B
Figure 8:
Mounting distances
If construction-conditioned the control cabinet cannot be without indoor ventilation, ap-
propriate filters must avoid suction of foreign objects.
Direction of the air
flow
Figure 9:
Control cabinet ventilation
42
C
D
Coolant inlet
=> 3.2.5
A lower value can be used here
Dimen-
Distance in mm
sion
A
150
B
100
C
30
D
0
X
50
1)
1)
Distance to preceding elements in the control cab-
inet door.
Front and side view of the coolant inlet
Coolant outlet
Distance in inch
6
4
1.2
0
2