DIMeNSIONS AND WeIGHTS

3.3.3 Through-mount version air cooler IP54

101
7,5
Housing size
Weight
Figure 6:
Dimensions through-mount version air cooler IP54
40
7,5
468
10x101=(505)
M5
520
IP54 zone: Heat sink underneath the mounting plate. For proper installation,
the enclosed seal (60F6T45-0002) must be installed between heat sink and
housing (e.g. cabinet wall). The tightness must be checked after the installa-
tion. If properly installed, the separation to the housing corresponds to degree
of protection IP54. However, the fans must be protected against unfavorable
environmental influences. These include combustible, oily or dangerous fumes
or gases, corrosive chemicals, coarse foreign bodies and excessive dust. This
applies especially to the access of the heatsink from the top (air outlet). Icing
is inadmissible.
IP20 zone: device above the mounting plate, power connections excluded =>
. This part is intended for the installation in a suitable
„Operating conditions"
housing for the required degree of protection (e.g. control cabinet).
UL: Unit heat sink is classified as NEMA type 1.
-
L2
L3
+
R
U
V
5 x 101 = (505)
101
11,5
480
6
20.6 kg