Terminal Block X1A Motor Connection; Figure 20: Terminal Block X1A Motor Connection - KEB COMBIVERT F6 Instructions For Use Manual

Installation f6 housing 6
Hide thumbs Also See for COMBIVERT F6:
Table of Contents

Advertisement

cONNecTION OF THe POWer UNIT

4.2.5.2 Terminal block X1A motor connection

X1A
L2
L3
+
-
R
L1
-
L1
L2
L3
+
R
Figure 20:
Terminal block X1A motor connection
ATTENTION
54
Name
U
V
W
U
V
W
U, V, W
M8 cable lugs with the following dimensions can be used for connections L1,
L2, L3, U, V, W:
max. width of 24 mm
max. shaft length 46 mm
max. diameter 19 mm
M8 cable lugs with the following dimensions can be used for connections +, -,:
max. width of 19 mm (e.g. tubular-cable-lugs by Weitkowitz Euro Series
with narrow flange).
max. shaft length 46 mm
max. diameter 19 mm
Alternatively to a 95 mm² line, 2 parallel 35 mm² lines can also be laid.
Short circuit due too low air and creepage distances!
► The pressing of the cable lugs must point upwards when connecting
95 mm² lines!
Terminal connec-
Function
8 mm stud for M8
Motor connection
cable lugs
Tightening
tion
torque
10...15 Nm
88...132 lb inch