Advertisement

INPUTS/OUTPUTS
5.9.8.2 Direct integer outputs
SETTINGS  INPUTS/OUTPUTS  DIRECT INTEGERS  DIRECT INTEGER OUTPUTS  DIRECT INTEGER 1(16) OUTPUT
 DIRECT INTEGER 1
 OUTPUT
The direct integer outputs share the direct input and output settings for device ID, data rate, ring configuration, and
channel crossover.
— This setting selects the FlexInteger parameter used to drive the associated direct integer output.
INTEGER 1 VALUE
INTEGER 1 TRIGGER
integer output. Transmission occurs on the rising edge of the operand. The operand must transition from 0 to 1 and remain
at a value of 1 for at least one power system cycle to ensure detection of the rising edge and transmission of the
associated direct integer output.
5.9.8.3 Direct integer inputs
SETTINGS  INPUTS/OUTPUTS  DIRECT INTEGERS  DIRECT INTEGER INPUTS  DIRECT INTEGER 1(16) INPUT
 DIRECT INTEGER 1
 INPUT
5
The direct integers feature allows the transmission of integer values between any two UR-series devices supporting the
feature. The communication channel is the same as that used for the direct inputs and outputs feature. When the direct
inputs/outputs, direct analogs, and direct integers features are used together on the same channel, the UR-series devices
must be using firmware version 5.70 or higher.
The settings for direct integer input 1 are as follows. The description applies to all 16 direct integer inputs.
DIRECT INTEGER 1 DEVICE
device programmed in this setting.
DIRECT INTEGER 1 NUMBER
integer input 1 is driven by the input programmed in this setting. This setting value corresponds to the direct integer output
number of the sending device.
DIRECT INTEGER 1 DEFAULT
offline and the
INTEGER 1 DEFAULT MODE
default mode is set to "Last Known," the value of direct integer input 1 remains at the last received value. This value is
stored as an unsigned 32-bit integer.

5.9.9 Teleprotection

5.9.9.1 Overview
The relay provides 16 teleprotection inputs on communications channel 1 (numbered 1-1 through 1-16) and 16
teleprotection inputs on communications channel 2 (on two-terminals two-channel and three-terminal systems only,
numbered 2-1 through 2-16). The remote relay connected to channels 1 and 2 of the local relay is programmed by
assigning FlexLogic operands to be sent via the selected communications channel. This allows the user to create
5-288
INTEGER 1 VALUE:
Off
INTEGER 1 TRIGGER:
Off
— This setting selects the FlexLogic operand used to trigger the transmission of the associated direct
DIRECT INTEGER 1
DEVICE: 0
DIRECT INTEGER 1
NUMBER: 0
INTEGER 1 DEFAULT:
1000.000
INTEGER 1 DEFAULT
MODE: Default Value
— This value selects the source of the direct integer 1 input. Direct integer input 1 is driven by the
— This value specifies which input to extract the value for the direct integer 1 input. Direct
— This setting specifies the value of direct integer input 1 when the associated direct device is
is set to "Default Value." When the associated direct device is offline and the
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: Off, any FlexInteger parameter.
See Appendix A for complete list.
Range: FlexLogic operand
Range: 0 to 16 in steps of 1
Range: 0 to 16 in steps of 1
Range: 0 to 429496295 in steps of 1
Range: Default Value, Last Known