CHAPTER 5: SETTINGS
5.7.6.3 Ground instantaneous overcurrent (ANSI 50G, IEC PIOC)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  GROUND CURRENT  GROUND IOC1(12)
 GROUND IOC1
The ground instantaneous overcurrent element can be used as an instantaneous element with no intentional delay or as a
definite time element. The ground current input is the quantity measured by the ground input CT and is the fundamental
phasor magnitude.
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
Figure 5-115: Ground TOC1 logic
GROUND IOC1
FUNCTION: Disabled
GROUND IOC1 SIGNAL
SOURCE: SRC 1
GROUND IOC1
PICKUP: 1.000 pu
GROUND IOC1 PICKUP
DELAY: 0.00 s
GROUND IOC1 RESET
DELAY: 0.00 s
GROUND IOC1 BLOCK:
Off
GROUND IOC1
TARGET: Self-reset
GROUND IOC1
EVENTS: Disabled
GROUPED ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: 0.020 to 30.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5
5-223