Flexlogic Equation Editor; N60 Network Stability And Synchrophasor Measurement System - Instruction Manual; Flexlogic Timers; Flexelements - GE N60 Instruction Manual

Network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
to the first "END" operator.
The "On" and "Off" operands can be placed in an equation to establish a known set of conditions for test purposes, and
the "INSERT" and "DELETE" commands can be used to modify equations.

5.6.5 FlexLogic equation editor

SETTINGS  FLEXLOGIC  FLEXLOGIC EQUATION EDITOR
 FLEXLOGIC
 EQUATION EDITOR
There are 1,024 FlexLogic entries available, numbered from 1 to 1024, with default END entry settings. If a "Disabled"
element is selected as a FlexLogic entry, the associated state flag is never set to '1'. Press the +/– key when editing
FlexLogic equations to quickly scan through the major parameter types.

5.6.6 FlexLogic timers

SETTINGS  FLEXLOGIC  FLEXLOGIC TIMERS  FLEXLOGIC TIMER 1(32)
 FLEXLOGIC
 TIMER 1
There are 32 identical FlexLogic timers available. These timers are used as operators for FlexLogic equations.
— Selects the time measurement unit.
TIMER 1 TYPE
— Sets the time delay to pickup. If a pickup delay is not required, set this function to "0."
TIMER 1 PICKUP DELAY
— Sets the time delay to dropout. If a dropout delay is not required, set this function to "0."
TIMER 1 DROPOUT DELAY

5.6.7 FlexElements

SETTINGS  FLEXLOGIC  FLEXELEMENTS  FLEXELEMENT 1(16)
 FLEXELEMENT 1
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
FLEXLOGIC ENTRY 1:
END
FLEXLOGIC ENTRY 1024:
END
TIMER 1
TYPE: millisecond
TIMER 1 PICKUP
DELAY:
0
TIMER 1 DROPOUT
DELAY:
0
FLEXELEMENT 1
FUNCTION: Disabled
FLEXELEMENT 1 NAME:
FxE 1
FLEXELEMENT 1 +IN:
Off
FLEXELEMENT 1 -IN:
Off
FLEXELEMENT 1 INPUT
MODE: SIGNED
FLEXELEMENT 1 COMP
MODE: LEVEL
FLEXELEMENT 1
DIRECTION: OVER
Range: FlexLogic operands
Range: FlexLogic operands
Range: millisecond, second, minute
Range: 0 to 60000 in steps of 1
Range: 0 to 60000 in steps of 1
Range: Disabled, Enabled
Range: up to six alphanumeric characters
Range: Off, any analog actual value parameter
Range: Off, any analog actual value parameter
Range: SIGNED, ABSOLUTE
Range: LEVEL, DELTA
Range: OVER, UNDER
FLEXLOGIC
5
5-183