COMMANDS MENU

7.1.4 Relay maintenance

COMMANDS  RELAY MAINTENANCE
 COMMANDS
 RELAY MAINTENANCE
This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are
activated by changing a command setting to "Yes" and pressing the
reverts to "No." The service command is activated by entering a numerical code and pressing the
PERFORM LAMP TEST
UPDATE ORDER CODE
order code to match. If an update occurs, the following message displays.
There is no impact if there have been no changes to the hardware modules. When an update does not occur, the ORDER
CODE NOT UPDATED message displays.
— Restarts the relay so that changes to configuration settings can take effect. In most cases, if changes are
REBOOT RELAY
made to the configuration settings these changes do not take effect unless the relay is rebooted.
With the CyberSentry option, the Administrator and Operator roles can initiate the Reboot Relay command.
SERVICE COMMAND
"20511" returns all settings to their factory default value. Code "101" is used to clear factory diagnostic information stored
7
in the non-volatile memory. If a code other than these two is entered, the command is ignored and no action is taken.
Various self-checking diagnostics are performed in the background while the N60 is running, and diagnostic information is
stored on the non-volatile memory from time to time based on the self-checking result. Although the diagnostic
information is cleared before the N60 is shipped from the factory, the user can want to clear the diagnostic information for
themselves under certain circumstances. For example, you clear diagnostic information after replacement of hardware.
Once the diagnostic information is cleared, all self-checking variables are reset to their initial state and diagnostics restart
from scratch.
SAVE VOLATILE DATA
recent as possible instead of relying on the periodic timer to save the data.

7.1.5 Phasor Measurement Unit one-shot

COMMANDS  PMU ONE-SHOT
 COMMANDS
 PMU ONE-SHOT
7-4
PERFORM LAMP TEST?
No
UPDATE ORDER CODE?
No
REBOOT RELAY?
No
SERVICE COMMAND
0
SAVE VOLATILE DATA?
No
— Turns on all faceplate LEDs and display pixels for a short duration.
— This command causes the relay to scan the backplane for the hardware modules and update the
UPDATING...
PLEASE WAIT
— Performs specific N60 service actions. Presently, there are two service actions available. Code
— Saves this data to compact flash memory prior to shutdown. This allows the saved data to be as
PMU ONE-SHOT
FUNCTION: Disabled
PMU ONE-SHOT
FRACTIONAL SEC: 0
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
CHAPTER 7: COMMANDS AND TARGETS
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: 0, 101
Range: No, Yes
key. The command setting then automatically
ENTER
ENTER
Range: Enabled, Disabled
Range: 0 to 99 in steps of 1
key.