CONTROL ELEMENTS
The CT failure function detects problems with system current transformers used to supply current to the relay. This logic
detects the presence of a zero-sequence current at the supervised source of current without a simultaneous zero-
sequence current at another source, zero-sequence voltage, or some protection element condition.
The CT failure logic (see later) is based on the presence of the zero-sequence current in the supervised CT source and the
5
absence of one of three or all of the three following conditions:
Zero-sequence current at different source current (can be different set of CTs or different CT core of the same CT)
Zero-sequence voltage at the assigned source
Appropriate protection element or remote signal
Settings are described as follows.
CT FAIL 1 FUNCTION
— Selects a FlexLogic operand to block operation of the element during some condition (for example, an
CT FAIL 1 BLOCK
open pole in process of the single pole tripping-reclosing). Local signals or remote signals representing operation of some
remote current protection elements via communication channels can also be chosen.
CT FAIL 1 3I0 INPUT 1
to the same source.
CT FAIL 1 3I0 INPUT 1 PICKUP
CT FAIL 1 3I0 INPUT 2
of the same CT. If 3I_0 does not exist at source 2, then a CT failure is declared.
CT FAIL 1 3I0 INPUT 2 PICKUP
CT FAIL 1 3V0 INPUT
CT FAIL 1 3V0 INPUT PICKUP
CT FAIL 1 PICKUP DELAY
5-256
CT FAIL 1 3I0 INP 1:
SRC 1
CT FAIL 1 3I0 INP 1
PKP: 0.2 pu
CT FAIL 1 3I0 INP 2:
SRC 2
CT FAIL 1 3I0 INP 2
PKP: 0.2 pu
CT FAIL 1 3V0 INPUT:
SRC 1
CT FAIL 1 3V0 INPUT
PKP: 0.20 pu
CT FAIL 1 PICKUP
DELAY: 1.000 s
CT FAIL 1 TARGET:
Self-reset
CT FAIL 1 EVENTS:
Disabled
— Enables or disables operation of the CT failure element.
— Selects the current source for input 1. The most critical protection element should also be assigned
— Selects the 3I_0 pickup value for input 1 (the main supervised CT source).
— Selects the current source for input 2. Input 2 should use a different set of CTs or a different CT core
— Selects the 3I_0 pickup value for input 2 (different CT input) of the relay.
— Selects the voltage source.
— Specifies the pickup value for the 3V_0 source.
— Specifies the pickup delay of the CT failure element.
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: 0.1 to 2.0 pu in steps of 0.1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: 0.1 to 2.0 pu in steps of 0.1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: 0.04 to 2.00 pu in steps of 0.01
Range: 0.000 to 65.535 s in steps of 0.001
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled