SYSTEM SETUP
PMU 1 TIMED TRIGGER POSITION
applies only to the timed mode of recording.
5.5.7.19 Aggregators
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PMU AGGREGATOR 1(4)
 PMU AGGREGATOR 1
5
When the protocol selection is set via the software or keypad, all aggregators whose protocol is not set to None are
set to the last protocol saved (that is, IEEE C37.118 or IEC 61850-90-5) to any aggregators, as both IEEE C37.118 and
IEC 61850-90-5 simultaneous streaming is not possible.
PMU AGGREGATOR1 PROTOCOL
protocol is supported at a time in a device, this setting applies to all PMU aggregators.
PMU AGGREGATOR1 IDCODE
identifies the ID of the aggregator, which is only used if there is more than 1 PMU mapped into an aggregator.
PMU AGGREGATOR1 PMU1
AGGREGATOR1 does not include PMU1 data set in the report if set to "No."
Only PMUs with same reporting rate can be assigned to the same PMU AGGREGATOR.
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PMU AGGREGATOR 1(4)  C37.118 AGGR 1(4)
CONFIGURATION
 C37.118 AGGR 1
 CONFIGURATION
5-162
— Specifies the amount of pre-trigger data as a percent of the entire record. This setting
PMU AGGREGATOR 1
PROTOCOL: NONE
PMU AGGREGATOR 1
IDCODE: 1
PMU AGGREGATOR 1
INCLUDE PMU1: No
PMU AGGREGATOR 1
INCLUDE PMU2: No
PMU AGGREGATOR 1
INCLUDE PMU3: No
PMU AGGREGATOR 1
INCLUDE PMU4: No
PMU AGGREGATOR 1
INCLUDE PMU5: No
PMU AGGREGATOR 1
INCLUDE PMU6: No
 C37.118 AGGR 1
 CONFIGURATION
 90-5 AGGR 1
 CONFIGURATION
— Selects if the IEEE C37.118 or IEC 61850-90-5 technical report is used. Because one
— Numeric identifier of the Aggregator / PDC function. In an IEEE C37.118 output stream, this
— If set to "Yes," aggregator 1 includes the PMU1 data set in the reporting data stream.
PMU AGGREGATOR 1
TCP PORT: 4712
PMU AGGREGATOR 1:
UDP PORT: 4713
PMU AGGREGATOR 1:
PDC CONTROL: Disabled
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: NONE, 37.118, 90-5
Range: 1 to 65534 in steps of 1
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
See below
See below
Range: 0 to 65534
Range: 0 to 65534
Range: Disabled, Enabled