CHAPTER 5: SETTINGS
I
is the measured overload RMS current at index n
n
E
is the accumulated energy at index n
n
E
is the accumulated energy at index n – 1
n – 1
The thermal overload protection element removes the
emergency, the thermal memory and
All calculations are performed per phase. If the accumulated energy reaches value 1 in any phase, the thermal overload
protection element operates and only resets when energy is less than 0.05 in all three phases.
Table 5-39: Typical time constants
Protected equipment
Capacitor bank
Overhead line
Air-core reactor
Busbar
Underground cable
The figure shows the logic for the thermal overload protection element.
5.8.11 Frequency rate of change (ANSI 81R)
SETTINGS CONTROL ELEMENTS FREQUENCY RATE OF CHANGE FREQUENCY RATE OF CHANGE 1(4)
FREQUENCY RATE
OF CHANGE 1
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
THERMAL PROT 1 OP
output operand can be reset using
THERMAL PROT 1 OP
Time constant
Minimum reset time
10 minutes
30 minutes
10 minutes
20 minutes
40 minutes
30 minutes
60 minutes
20 minutes
20 to 60 minutes
60 minutes
Figure 5-142: Thermal overload protection logic
FREQ RATE 1
FUNCTION: Disabled
FREQ RATE 1 SOURCE:
SRC 1
FREQ RATE 1 TREND:
Increasing
FREQ RATE 1 PICKUP:
0.50 Hz/sec
output operand when E < 0.05. In case of
THERM PROT 1 RESET
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: Increasing, Decreasing, Bi-directional
Range: 0.10 to 15.00 Hz/sec in steps of 0.01
CONTROL ELEMENTS
setting.
5
5-261