1 SAFETY INSTRUCTIONS

1.1

Operator precautions

The user must follow the precautions and only perform the described operations. Also in these measures the
operator of the UPS system must adhere to the instructions in this manual. Any deviations from the
instructions could be dangerous to the user or cause accidental load loss.
The only user operations permitted are:
- Use of the LCD control panel (LCD Display) and Maintenance Bypass (if present)
- Start up and shut down of the UPS (excluding the commissioning start up)
- Operation of additional connectivity devices
THE SUPPLIER DOES NOT TAKE ANY RESPONSIBILITY FOR DAMAGES CAUSED THROUGH WRONG
MANIPULATIONS OF THE UPS SYSTEM.
WARNING!
WARNING!
WARNING!
1.2

Environmental Considerations

To operate the UPS at its best efficiency point, your installation site should meet the environmental
parameters outlined in this manual. Excessive amount of dust or moisture in the operating environment may
cause damage or lead to malfunction. The UPS should be always protected from the outside weather and
sunshine. The operating environment must meet the weight, airflow, size and clearance requirements
specified in the technical datasheet.
Under no circumstances the UPS should be installed in an airtight room, in the presence of flammable gases,
or in an environment exceeding environmental requirements here below.
An ambient temperature of +20°C to +25°C is recommended to achieve a long life of the UPS and batteries.
The cooling air entering the UPS must not exceed +40°C and the humidity should be below 95% (non-
condensing).
1.3

Declaration of Safety conformity and CE marking

PowerValue 11 RT is designed, manufactured and commercialized in accordance with the standard of
Quality Management Systems EN ISO 9001. The marking shows the conformity to the EEC Directive by
means of the application of the following standards in accordance with the specifications of the harmonized
standards:
• 2006/95/EC Low voltage directive.
• 2004/108/EC Electromagnetic Compatibility directive (EMC).
Standards as reference:
• EN-IEC 62040-1. Uninterruptible power supply (UPS). Part 1-1: General and safety requirements for UPS's
used in accessible areas by end users.
IT IS PROHIBITED TO REMOVE ANY SCREWS FROM THE UPS
SYSTEM OR FROM THE BATTERY CABINET: DANGER OF
ELECTRICAL SHOCK.
HIGH FAULT CURRENTS (LEAKAGE CURRENTS):
BEFORE CONNECTING THE MAINS YOU MUST ENSURE THAT THERE
IS A PROPER EARTH CONNECTION!
THE USER MUST DISPLAY A WARNING SHIELD ON ALL PRIMARY
UPS CIRCUIT BREAKERS. THE SERVICE PERSONNEL HAS TO BE
INFORMED ABOUT DANGEROUS VOLTAGES. THE WARNING PANELS
MUST CONTAIN THE FOLLOWING TEXT: "BEFORE STARTING WITH
THE MAINTENANCE WORK ON THE CIRCUIT BREAKERS, MAKE SURE
THE UPS IS ISOLATED."
04-3788_ABB_OPM_PVA11 6-10kVA-RT_EN_140423
Modifications reserved
Page 6/37 ABB