Important Safety Instructions; Operator Precautions; Environmental Considerations; Declaration Of Safety Conformity And Ce Marking - ABB PowerValue 11T IN User Manual

Hide thumbs Also See for PowerValue 11T IN:
Table of Contents

Advertisement

6
POWERVALUE 11T IN — 6-10 KVA

1. Important safety instructions

1.1 Operator precautions

Always follow the precautions and instructions
described in this manual. Any deviations from the
instructions may result in electric shock or cause
accidental load loss.
ABB does not take any responsibility for
damages caused through incorrect use of the
UPS system.
DANGER!
Read this important safety instruction chapter before reading the
operating manual
Do not remove any screws from the
UPS system or from the battery
cabinet: danger of electrical shock.
High fault currents (leakage
currents) before connecting the
mains, ensure that the UPS is
earthed!
Display a warning label on all
primary power isolators installed
away from the UPS area to warn
electrical maintenance personnel
that the circuit feeds a UPS.
Make sure that warning label
contains the following text or
Equivalent: Isolate the UPS
(Uninterruptible Power Supply)
before working on this circuit.

1.2 Environmental considerations

To operate the UPS with optimal efficiency, your
installation site should meet the environmental
parameters outlined in this user manual.
Excessive amounts of dust or moisture in the
operating environment may cause damage or
lead to malfunction. The UPS should always be
protected from the weather and sunshine.
The operating environment must meet the
weight, airflow, size and clearance requirements
specified in the technical datasheet.
Under no circumstances, should the UPS be
installed in an airtight room, in the presence of
flammable gases, or in an environment exceeding
the environmental requirements specified below.
An ambient temperature of +20°C to +25°C is
recommended to achieve a long life of the UPS
and batteries. The cooling air entering the UPS
must not exceed +40 °C and the humidity should
be below 95 percent (non-condensing).
1.3 Declaration of safety
conformity and CE marking
The PowerValue 11T 1-3 kVA is designed,
manufactured and commercialized in accordance
with the EN ISO 9001 standard relating to quality
management systems.
These products conform with the following
directives:
2014/35/EU Low voltage directive
2014/30/EU Electromagnetic Compatibility
directive (EMC)
2011/65/EU Restriction of the use of certain
hazardous substances (RoHS) directive
WARNING!
This is a category C2 UPS product.
In a residential environment, this
product may cause radio
interference, in which case the user
may be required to take additional
measures.

Advertisement

Table of Contents
loading

Table of Contents