2.5

Init/Normal Dip-switch

On the back of the I-7530A module, there is a dip-switch used for
setting the operation or configuration mode of the module function. In the
normal situation, the user needs to first make a configuration in order to
provide the correct function when the module works in the operation mode.
The following steps show how to use this dip-switch.
(1) Configuration mode: Please first set the dip-switch to the "Init" (Initial)
position. Then the I-7530A will work in the configuration mode after
the power for the module has been turned on. In this case, users can
configure the communication parameters of the I-7530A module by
using the I-7530 Utility tool.
(2) Operation mode: After the configuration, users need to set the dip-
switch to the "Normal" position. Users need to turn the power off then
on again so that they can use the I-7530A in the operation mode.
Once you have completed your configurations and have switched to
the operation mode, then messages can pass between the CAN and
the RS-232/485/422. This transmission process depends on the
configuration parameters that the users have configured. That is, the I-
7530A functions as a RS-232/485/422 to CAN converter.
I-7530A RS-232/485/422 to CAN Converter User's Manual (Version 1.2, Sep/2011) ------------- 10
Figure 7: Dip-switch of I-7530A